215kWh All-in-One C&I BESS
IEC62619 / CE / UN38.3
F215C All-in-one C&I Battery Energy Storage System highly integrates PACK, BMS, EMS, PCS, STS, air-conditioner and fire-fighting system by modular design. It supports both on-grid and off-grid applications, bringing low-carbon, high-yield solution to industrial and commercial customers.

Advantages
High Integration
Highly integrated PACK, BMS, EMS, PCS, STS, air-conditioner and fire fighting system, with an all-in-one design
High Safety
- LiFePO4 cell, high thermal stability.
- Three-level active protection system, accurately monitoring short circuit, over-current, over-voltage, over-temperature and other abnormalities.
- Two levels of passive protection system.
High Adaptability
- 3L+N+PE wiring system, can be used both grid-tied and off grid, supporting 100% unbalanced load output.
- Optional 300kW STS, supporting seamless switching between on-grid and off-grid ≤20ms.
- Off-grid black start function.
Intelligent Management
- Built-in EMS, with cloud platform to achieve remote monitoring, remote settings, revenue calculation, remote upgrade, data analysis, cloud warning and other functions.
- Local display is convenient for on-site operation and maintenance.
Technical Specifications
Model | F215C | |
---|---|---|
System | Nominal capacity | 280Ah |
Nominal energy | 215kWh | |
Usable energy | ≥200kWh | |
Rated output power | 100kW | |
IP rating | IP54 | |
Operating temperature | -20℃~55℃ | |
Cooling mode | Air cooling | |
Fire protection | Aerosol | |
Altitude | 4000m(>2000m derate) | |
Cycle life | ≥6000 cycles | |
Dimensions (W*D*H) | 1600*1300*2200mm | |
Weight | ≈2900kg | |
Certification | IEC62619/CE/UN38.3 | |
AC (on-grid) | Nominal voltage | 400V |
Nominal output current | 145A | |
AC access method | 3L+N+PE | |
Grid voltage range | 400V(-20% ~ +15%) | |
Grid frequency range | 50Hz/60Hz±2.5Hz | |
Power factor | -0.99 ~ +0.99 | |
DC component | ≤0.5%In | |
On/off grid switching time | 20ms, with STS (optional) | |
AC (off-grid) | AC off-grid voltage | 400V |
AC voltage range | 400V±3% | |
AC off-grid frequency | 50Hz/60Hz | |
Off-grid output THDU | ≤3% (linear load) | |
Unbalanced load capacity | 100% | |
DC | DC voltage range | 672V ~ 876V |
Nominal power | 100kW | |
DC maximum current | 160A |